ELEVATOR SITE REQUIREMENT
1) The temperature of the machine room and elevator hoist-way shall be below 40˚C.
2) The following conditions are required for maintaining elevator performance.
a. The relative humidity shall be below 90% on a monthly average and below 95% on a daily average.
b. Prevention shall be provided against icing and condensation occurring due to a rapid drop in the
temperature in the machine room and elevator hoist-way.c. The machine room and the elevator hoist-way shall be finished with mortar or other materials so as to
prevent concrete dust.3) Voltage fluctuation shall be within a range of 5% ~ 10%.
WORKS NOT INCLUDED IN ELEVATOR CONTRACT
The following items are excluded from elevator installation work, and are therefore the responsibility of the building owner or general contractor –
1) Construction of the elevator machine room with proper beams and slabs, equipped with a lock, complete with illumination, ventilation and waterproofing.
2) Access to the elevator machine room sufficient to allow passage of the control panel and traction machine.
3) Architectural finishing of the machine room floor, and the walls and floors in the vicinity of the entrance hall after installation has been completed.
4) Construction of an illuminated, ventilated and waterproofed elevator hoist-way.
5) Provision for cutting the necessary openings and joists.
6) Separate beams, when the hoist-way dimensions markedly exceed the specifications, and intermediate beams for Duplex system.
7) The machine room power-receiving panel and the electrical wiring for illumination, plus the electrical wiring from the electrical room to the power-receiving panel.
8) The power consumed in installation work and test operations.
9) All the necessary building materials for grouting in of brackets, bolts, etc.
10) The test provision and subsequent alteration as required, and eventual removal of the scaffolding as required by the elevator contractor, and any other protection of the work as may be required during the progress.
11) The provision of a suitable, locked space for the storage of elevator equipment and tools during elevator installation.
12) The security system, such as a card reader, connected to controller, when supplied by the building owner or general contractor.
** Work responsibilities in installation and construction shall be determined according to W.B. laws.